5 Troubleshooting
5
Fault Code Name Possible Causes Solution Level
Err07
Overvoltage at
constant speed
The input voltage is
too high.
⢠Check whether the input voltage is too high.
⢠Observe whether the bus voltage is too high
(normal: 540 to 580 V for 380 voltage input).
5A
The resistance of
the braking resistor
is excessive, or the
braking unit fails.
⢠Check for the balance coefīæcient.
⢠Check whether the bus voltage rises too
quickly during running. If yes, the braking
resistor does not work or its model is
improper:
a. Check whether the cable connecting the
braking resistor is damaged, whether the
cooper wire touches the ground, and whether
the connection is reliable.
b. Check whether the resistance is proper
based on the recommendation and select a
proper braking resistor.
If the resistance of the braking resistor is
proper and overvoltage occurs each time
when the elevator reaches the target speed,
decrease the values of F2-01 or F2-04 to
reduce the curve following error and prevent
overvoltage due to system overshoot.
Err08
Maintenance
notiīæcation
period reached
The elevator is not
maintained within the
notiīæcation period.
1. Power-off and maintain the elevator.
2. Disable the maintenance notiīæcation function
by setting F9-13 to 0.
3. Contact us or our agent directly.
5A
Err09
Undervoltage
Instantaneous power
failure occurs on the
input power supply.
⢠Check whether the power fails during
running.
⢠Check whether wiring of all power input
cables is secure.
5A
The input voltage is
too low.
Check whether the external power voltage is
too low.
The drive control
board fails.
Contact our agent or Inovance directly..