- 138 -
5 Troubleshooting
5
Fault Code Name Possible Causes Solution Level
Err35
Shaft auto-tuning
data abnormal
Subcode 101: When
shaft auto-tuning is
started, the elevator is
not at the bottom oor
or the down slow-
down switch is invalid.
Check that the down slow-down switch is valid,
and that F4-01 (Current oor) is set to the
bottom oor number.
4C
Subcode 102: The
system is not in the
inspection state
(inspection switch
not turned on) when
shaft auto-tuning is
performed.
Check that the inspection switch is turned to
inspection state.
Subcode 103: It is
judged upon power-on
that shaft auto-tuning
is not performed.
Perform shat auto-tuning again.
Subcode 104, 113,
114: In distance
control mode, it is
judged at running
startup that shaft
auto-tuning is not
performed.
Subcode 105: The
elevator running
direction and the
pulse change are
inconsistent.
Check whether the elevator running direction is
consistent with the pulse change in F4-03: F4-
03 increases in up direction and decreases in
down direction. If not, change the value of F2-
10 to ensure consistency.
Subcodes 106, 107,
109: =The plate pulse
length sensed at
up/down leveling is
abnormal.
• Check that NO/NC state of the leveling
sensor is set correctly.
• Check whether the leveling plates are
inserted properly and whether there is strong
power interference if the leveling sensor
signal blinks.
Subcodes 108, 110:
No leveling signal is
received within 45s
continuous running.
• Check whether wiring of the leveling sensor
is correct.
• Check whether the oor distance is too large,
causing running time-out. Increase the speed
set in F3-11 and perform shaft auto-tuning
again to ensure that learning the oors can
be completed within 45s.
Subcodes 111, 115:
The stored oor
height is smaller than
50 cm.
Enable the super short oor function if the oor
distance is less than 50 cm.
If the oor distance is normal, check installation
of the leveling plate for this oor and check the
sensor.
Subcode 112: The
oor when auto-tuning
is completed is not
the top oor.
Check whether the setting of F6-00 (Top oor of
the elevator) is correct and whether the leveling
plate is absent.