- 82 -
4 Parameter Description
4
Parameter
No.
Parameter Name Setting Range Default Unit
Property
F3-08 is used to set the deceleration rate in elevator slow-down, inspection, and shaft auto-tuning.
This parameter is not used during normal running. It is used only when the elevator position is abnormal or the
slow-down signal is abnormal.
The system automatically detects the speed when the elevator reaches a slow-down switch. If the detected speed
or position is abnormal, the system enables the elevator to slow down at the special deceleration rate set in F3-
08, preventing over travel top terminal or over travel bottom terminal.
F3-09 is used to set the pre-deceleration distance of the elevator in distance control, as shown in Figure 4-2. This
function is to eliminate the effect of encoder signal loss or leveling signal delay.
F3-10 Re-leveling speed 0.020 to 0.080 0.040 m/s
ā
It is used to set the elevator speed during re-leveling. This parameter is valid only when the pre-open module
(MCTC-SCB-A) is added to implement the re-leveling function (set in FE-32).
F3-11 Inspection speed 0.100 to 0.630 0.250 m/s
ā
It is used to set the elevator speed during inspection and shaft auto-tuning.
F3-12
Position of up slow-down
1
0.00 to 300.00 0.00 m
ā
F3-13
Position of down slow-
down 1
0.00 to 300.00 0.00 m
ā
F3-14
Position of up slow-down
2
0.00 to 300.00 0.00 m
ā
F3-15
Position of down slow-
down 2
0.00 to 300.00 0.00 m
ā
F3-16
Position of up slow-down
3
0.00 to 300.00 0.00 m
ā
F3-17
Position of down slow-
down 3
0.00 to 300.00 0.00 m
ā
F3-18
Zero-speed control time
at startup
0.200 to 1.000 0.200 s
ā
F3-19 Brake release delay 0.000 to 2.000 0.600 s
ā
F3-20
Zero-speed control time
at end
0.000 to 1.000 0.300 s
ā