6 Parameter Description
-
203
-
00: Invalid
The terminal has no function.
01: Running contactor control
02: Brake contactor control
03: Shorting door lock circuit contactor control
The terminal with one of these signals controls whether the contactor is opened or
closed.
󶍿
󶍾
󶍾󶍿
05: Door machine 1 open
06: Door machine 1 close
07: Door machine 2 open
08: Door machine 2 close
The terminal with one of these signals is used to control open and close of door 1 or 2.
09: Brake and RUN contactors healthy
When the brake and RUN contactors operate properly (non-E36/E37 state), the system
sends the feedback signal for monitoring.
10: Fault state
The terminal with the signal has output when the system is in the level-3, level-4 or
level-5 fault state.
11: Running monitor
The terminal with the signal has output when the controller is running.
12: Shorting PMSM stator contactor
When the shorting PMSM stator contactor is applied in synchronous motor, the
terminal with the signal is used to control whether the contactor is closed or opened.
13: Emergency evacuation automatic switchover
When detecting that the bus voltage declines to a certain value after power failure
occurs on the mains supply, the controller outputs this signal and uses the battery for
temporary power supply, implementing emergency evacuation running.
Only Y6/M6 can be allocated with this signal because the controller needs to depend
on its residual power to drive the relay at power failure of the mains supply.
14: System healthy
The terminal with the signal has output when the system operates properly.
15: Emergency buzzer control
The terminal with the signal has output when the system is in the emergency
evacuation running state. The buzzer tweets to prompt.