9 Description of Functions and Schemes 
- 
323
 -
9.13 Automatic Emergency Evacuation Scheme at Power Failure
1  Background
Passengers may be trapped in the car if power failure happens during use of the 
solve the problem.
2  Overview
Scheme 1: UPS standby power supply (220 V)
In this scheme, the 220 V UPS provides power supply to the motor and the drive 
control circuit.
Scheme 2: Automatic rescue device (ARD) for elevator emergency evacuation
In this scheme, the ARD provides power supply to the motor and the drive control 
circuit.
manual for the ARD. This part describes only Monarch elevator ARD.
Automatic 
Emergency 
Evacuation 
Scheme
Principle
Emergency 
evacuation by 
controller drive
After the mains power supply shuts down, the standby power supply is 
used to provide power to the system. The controller drives the motor, 
which runs the car to the leveling area to let passengers out.
Emergency 
evacuation by 
shorting stator 
braking
After the mains power supply shuts down, the standby power supply is 
used to provide power to the system. The controller shorts the motor 
stator and releases the brake, making the car move slowly under the 
to the leveling area to let passengers out.
There are two standby power supply modes in the industry.                             
Standby Power 
Supply
Description
Emergency 
evacuation by 
controller drive
The (UPS) is used.
The UPS RUN contactor and UPS control circuit must added in the 
control cabinet.
Automatic rescue 
device (ARD) 
for elevator 
emergency 
evacuation 
The battery is used as the standby power supply. Only the input terminal 
for emergency evacuation signal feedback must be reserved in the 
control cabinet. There is no other cost.
The ARD itself has the control system which can diagnose the mains 
power supply status and performs emergency evacuation running.