Appendix A Foreign Standards 
- 
345
 -
A.4.2 System Wiring Requirements
1)  The motor cables must be far away from other cables. Recommended distance is 
bigger than 0.5 m. The several controllers can be laid in parallel.
2)  It is recommended that the motor cables be protected in the metal sheathing or 
cabling duct with metal plate; both sides of the metal jacket and cabling duct 
must be grounded reliably.
Shielded 
drive cable
Metal jacket
Shielded 
drive cable
Metal cable 
trunking
3)  To avoid electromagnetic interference caused by rapid change of the output 
voltage of the controller, the motor cables and other cables must not be laid side 
by side for a long distance. It is recommended that the motor cables, power input 
in good connection and well grounded.
4)  If the control cable must run across the power cable, make sure they are arranged 
at an angle of close to 90° . Do not run other cables above the controller.
5)  The power input and output cables of the controller and weak-current signal 
cables (such as control wires) should be laid vertically (if possible) rather than in 
parallel.
6)  The cable trunking must be in good connection and well grounded. Aluminum 
trunking can be used to improve electric potential.
7)  The controller must be in good contact with the control cabinet. The contact area 
is coated to ensure good conductivity.
8)  The motor must be in good contact with the system. The contact area is coated to 
ensure good conductivity.
 
NICE3000
new
integrated 
elevator controller
Control & encoder cable
Communication cable
Power cable
Communication cable
 Control cable
Encoder cable
 
Power cable
 
Motor cable
 Min. 300 mm
 Min. 200 mm
90°
90°
 Min. 500 mm
 Control cable
Cabling requirements