9 Description of Functions and Schemes 
- 
335
 -
HCB addresses of front door: 1 to 15 
HCB+16 addresses of back door: 17 to 31
3  Parameters
Type
Door Control 
Mode
Parameter Setting
Service
Floor
Operation 
Box CCB 
Wiring
HCB 
Address 
Setting
Mode 
Selection
Other 
Parameters
Mode 1
Simultaneous 
control
FC-04 = 0
FB-00 = 2 (CTB 
analog input)
FE-33 Bit15 = 1
15
The CCB of 
front door is 
connected 
to CN7 on 
the CTB.
The CCB of 
back door is 
connected 
to CN8 on 
the CTB.
HCB 
address 
of front 
door: 
HCB 
address 
of back 
door: 
Mode 2
Hall call 
independent, 
car call 
simultaneous
FC-04 = 1 Same as mode 1 15
Mode 3
Hall call 
independent, 
car call 
manual
control
FC-04 = 2 (CTB 
analog input)
F6-40 Bit4 = 1
Same as mode 1 15
Mode 4
Hall call 
independent, 
car call 
independent
FC-04 = 3 Same as mode 1 15
The CCB of 
front door is 
connected 
to CN7 on 
the CTB. 
The CCB of 
back door is 
connected 
to the CCB 
of front door 
in cascade.
In mode 3, the car door to open is controlled as follows:
 
◆
The control switch is connected to JP16 on the CCB. When JP16 is ON, only the front door 
opens; when JP16 is OFF, only the back door opens.