Appendix A Foreign Standards
- 
344
 -
A.4 Requirements on Cables and Cabling
A.4.1 Requirements for Shielded Cable
1)  Use the shielded cable to connect the motor to meet the EMC requirements. The 
4-conductor shielded cable is recommended with one conductor as the PE. If the 
3-conductor shielded cable is used and the shield cannot meet the conduction 
requirements, an additional PE wire must be added.
 
■
Recommended cables:  
PE
 
Shield
 PE conductor
and shield
PE
 Shield
Cross section of recommended shielded cables
 
■
Non-recommended power cables:
Cross section of non-recommended shielded cables
2)  To suppress emission and conduction of the radio frequency interference 
and conductivity. as shown in Figure A-4.
 Cable core
 Internal insulator
 Copper braid
 Copper shield
 Insulation jacket
Braided density of shield
3)  The grounding area of the shielded cable must be as large as possible. Fasten the 
shield to the metal plate with the metal cable clamp, as shown in the following 
Metal plateMetal cable clampShielded cable
Fastening the shield with the metal cable clamp