- 115 -
4 Parameter Description
4
Parameter
No.
Parameter Name Setting Range Default Unit
Property
FC-01 is used to set program control related to protection functions. Each bit of the parameter denes a function,
as described in the following table.
If a bit is set to 1, the function indicated by this bit is enabled; if this bit is set to 0, the function is disabled. For
details on how to view and set this parameter, see the descriptions in section 8.21.1.
The functions dened by the binary bits of FC-01 are described in the following table.
Bit Function Description Default
Bit0 Overload protection It sets whether to implement overload protection. 1
Bit1
Canceling protection at
output phase loss
It sets whether to implement protection at output phase loss. 0
Bit4
Light curtain judgment at
door close limit
At door close limit, the door re-opens if the light curtain is valid. 0
Bit5
Canceling SPI
communication judgment
It sets whether to implement wire-breaking detection on SPI
communication between the MCB and the drive board.
0
Bit6
to
Bit8
Reserved - 0
Bit14
Canceling protection at
input phase loss
It sets whether to implement protection at input phase loss. 0
FC-02
Overload protection
coefcient
0.50 to 10.00 1.00 -
FC-03
Overload pre-warning
coefcient
50 to 100 80 %
FC-04 Opposite door selection
0: Simultaneous control
1: Hall call independent, car call
simultaneous
2: Hall call independent, car call
manual control
3: Hall call independent, car call
independent
0 -
FC-11
Logic information of
designated fault
0 to 9999 0 -
FC-12
Curve information of
designated fault
0 to 65535 0 -
FC-13
Set speed upon
designated fault
0 to 1231 0 MM.DD
FC-14
Feedback speed upon
designated fault
0 to 23.59 0 HH.MM
FC-15
Bus voltage upon
designated fault
0 to 9999 0 -
FC-16
Current position upon
designated fault
0 to 65535 0 -
FC-17
Output current upon
designated fault
0 to 1231 0 MM.DD
FC-18
Output frequency upon
designated fault
0 to 23.59 0 HH.MM
FC-19
Torque current upon
designated fault
0 to 9999 0 -
FC-20 1st fault code 0 to 65535 0 -