- 123 -
4 Parameter Description
4
Parameter
No.
Parameter Name Setting Range Default Unit
Property
Fr-20
Leveling adjustment
record 20
0 to 60060 30030 mm
★
Fr-01 to Fr-20 record the leveling adjustment values. Each parameter records the adjustment information of two
oors, and therefore, the adjustment information of 40 oors can be recorded totally.
The method of viewing the record is shown in the following gure.
Figure 4-10 Viewing the leveling adjustment record
Second floor leveling First floor leveling
...
...
> 30: upward leveling adjustment
= 30: no leveling adjustment
< 30: downward leveling adjustment
Maximum
adjustment
range: ±30mm
As shown in the preceding gure, the left two LEDs and the right two LEDs respectively show the adjustment
bases of the rst oor and second oor. If the value is larger than 30, it is upward leveling adjustment; if the value
is smaller than 30, it is downward leveling adjustment. The default value “30” indicates that there is no leveling
adjustment. The maximum adjustment range is ±30 mm.
The leveling adjustment method is as follows:
Ensure that shaft auto-tuning is completed successfully, and the elevator runs properly at normal speed.
Set Fr-00 to 1 to enable the car leveling adjustment function. Then, the elevator shields hall calls, automatically
runs to the top oor, and keeps the door open after arrival. If the elevator is at the top oor, it directly keeps the
door open.
Go into the car, press the top oor button on the CCB once, and the leveling position is changed 1 mm upward;
press the bottom oor button on the CCB once, and the leveling position is changed 1 mm downward. The value
is displayed on the car display board.
Positive value: up arrow + value, negative value: down arrow + value, adjustment range: ±30 mm
After completing adjustment for the present oor, press the top oor button and bottom oor button at the same
time to save the adjustment result. The car display restores to the normal state. If the leveling position of the
present oor need not be adjusted, press the top oor button and bottom oor button at the same time to exit the
leveling adjustment state. Then, car calls can be registered.
Press the door close button, and press the button for the next oor. The elevator runs to the next oor and keeps
the door open after arrival. Then, you can perform leveling adjustment.
After completing adjustment for all oors, set Fr-00 to 0 to disable the leveling adjustment function. Otherwise, the
elevator cannot be used.
Group E0: 1st fault details
The system prompts and records faults. The keypad displays the fault code and subcode in scrolling mode, for
example, “ E22-101
E0-00 1st fault code 0 to 9999 0
●
E0-01 1st fault subcode 0 to 65535 0
●