DISTRIBUTION PANEL
The EMS Distribution Panel should be installed in a convenient location where it can get air circulation to keep it from over
heating. There should be a minimum of 7" of depth behind the mounting surface to provide enough room for the box and
wiring.
Cut a hole in the mounting panel as shown here:
Carefully cut opening, allowing enough wood to hold enough clearance around the box
for the front cover screws.
The wiring to the box should be routed through the holes in the back and secured using approved cable connectors. The
wires should be with the appropriate size and insulation to meet N.E.C. requirements.
The main supply cable should be brought through the large hole in the lower center of the box and secured with an
appropriate connector. The "LINE 1" and "LINE 2" supply mains should be connected to the corresponding Main Breaker.
The Main Ground lead should be connected to the nearest GROUND bar terminal strip. The current sensor should be
mounted in a knock-out hole near the insulated NEUTRAL block, so that the signal leads from the current sensor exit the
rear of the box. These signal wires should be routed through the lower right hole into the low voltage section of the EMS
and connected to J3 (a 2-pin connector on the low voltage side of the Control Module). The inverter/converter should be
wired so that the AC input to the inverter/converter is supplied via a branch breaker on the Main Distribution Panel and the
120 VAC output of the inverter/converter wired to the individual lug on the far right side of the sub-panel.
The Main NEUTRAL wire should be routed through the CURRENT SENSOR and connected to an appropriate position on
the insulated NEUTRAL block.
There are 8 positions for circuit breakers on the Main Distribution Panel and 3 positions for circuit breakers on the Sub-
Panel in the box. The circuit breakers can be single or dual types. The breakers in the two center positions of the Main
Distribution Panel be rated at 50Amps to be used as the Main Breakers.
Eaton Cutler-Hammer: BR, BD, GFCB, Filler Plate BRFP
Siemens-DPD: QP, QT, Filler Plate QF3
the mounting screws and to allow
Copper conductors ONLY,
MUST
The following breakers are suitable for MAIN and BRANCH breakers:
Replacement circuit breakers must be of the same type and rating.
7
131 Eisenhower Lane North
Lombard, IL 60148
630.268.0010 / 1.800.251.2408
50 AMP Smart Energy Management System Model 800
TM
P/N 53-00894-100 Rev. E 030807