EasyManuals Logo

Intergas Compact HRE 18 SB User Manual

Intergas Compact HRE 18 SB
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
Intergas Heating Ltd 28
9 COMMISSIONING THE APPLIANCE
At the time of commissioning, complete all relevant sections of the Benchmark
Checklist located in section 17 of this document.
9.1 Filling and venting the appliance and the installation
9.1.1 CH system
CAUTION
When an additive is added to the CH water, ensure it is
suitable for the materials used in the appliance, such as
copper, brass, stainless steel, steel, plastic and rubber.
1. Connect to 3 amp fused spur, or via a three pin plug to an unswitched socket.
2. Connect the appliance to mains.
The appliance may perform a self test: 2 (on service display).
The appliance will then go into wait mode: - (on service display).
14. Connect the filling loop and fill the installation with clean drinking water to a
maximum pressure of 1-2 bar in the case of a cold installation. (Indicated on the
temperature display.)
15. Bleed the appliance with the manual bleed screw (A).
An automatic air bleeding device may be fitted to the appliance in place of the
manual bleed screw.
16. Bleed the air in the installation with the manual bleed screws on the radiators.
17. Top up the CH installation if the pressure has dropped too far as a result of the
air bleeding.
18. Check all couplings for leakage.
19. Fill the condensate trap with water.
9.1.2 Hot water supply (only when an indirectly heated DHW storage
cylinder is applied)
1. Open the main tap to pressurise the hot water section.
2. Vent the exchanger and the pipe system by opening a hot water tap.
3. Leave the tap open until all air has disappeared from the system.
4. Check all connections for leaks including internal connections.
9.1.3 Gas supply
1. Gas supply purged of air via test point D on gas valve (see illustration )
2. Connect a suitable gauge to test point D .
Static or standing pressure must be 20mb. If 20mb is not obtained
DO NOT proceed with commissioning until supply is rectified.
3. If static pressure is correct fire the boiler and allow to reach working
temperature.
4. Test working pressure by selecting test program “H”. See section 10.8, High
Setting. Working pressure must be 20mb +or- 1mb.
If working pressure is less than 19mb appliance heat output will be reduced and
correct combustion readings may not be obtained. Do not adjust the air/gas
ratio. Correct gas supply to obtain sufficient working pressure.
NOTE
The inlet working pressure must be obtained with all other gas
appliances at the property working.

Table of Contents

Other manuals for Intergas Compact HRE 18 SB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Intergas Compact HRE 18 SB and is the answer not in the manual?

Intergas Compact HRE 18 SB Specifications

General IconGeneral
BrandIntergas
ModelCompact HRE 18 SB
CategoryWater Heater
LanguageEnglish