EasyManua.ls Logo

Intertek TASMAN EP & HP - Page 17

Intertek TASMAN EP & HP
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 17 of 80
3.3.4 Top Vent - Direct Vent Information (continued)
Selkrik Direct-Temp Venting
The minimum vent system for horizontal termination must consist of:
Simpson Dura-Vent adapter Part # 0924N3 directly on top of unit
90 degree elbow
12" (305 mm) length horizontally
Wall thimble part #IMC1082A
Horizontal termination cap 4DT-HC
The maximum horizontal vent system consists of:
Simpson Dura-Vent adapter Part # 0924N3 directly on top of unit
40' (12192 mm) vertical length directly on top of the stove
90 degree elbow
15' (4572 mm) maximum horizontal length
Wall thimble part# IMC1082A
Horizontal termination cap 4DT-HC
The maximum vertical system consists of:
Simpson Dura-Vent adapter Part # 0924N3 directly on top of unit
Up to 40' (12192 mm) of vertical length
Fire stop
Flashing
Collar
Termination cap part # 4DT-VC
Use a ceiling fire stop when penetrating a ceiling or floor. Use a wall thimble when penetrating an
inside wall or outside wall. Vent terminals shall not be recessed into a wall or siding.
Do not exceed more than 15' (4572 mm) of horizontal length of vent.

Related product manuals