List of Function Parameters 
 
96
Function 
Code 
Name  Description 
Factory 
Setting
Modify 
Serial 
No. 
P7.19 
Output terminal 
status at current fault 
BIT3  BIT2  BIT1  BIT0 
   R0  Y 
  ●  96 
P8 Group: Enhanced Function 
P8.00  Acceleration time 1  0.1~3600.0s 
Depend 
on model
O  97 
P8.01  Deceleration time 1  0.1~3600.0s 
Depend 
on model
O  98 
P8.02 
Jog reference  0.00~P0.04 
5.00Hz
O  99 
P8.03 
Jog acceleration time  0.1~3600.0s 
Depend 
on model
O  100 
P8.04 
Jog deceleration time  0.1~3600.0s 
Depend 
on model
O  101 
P8.05 
Skip frequency  0.00~P0.04  0.00Hz
O  102 
P8.06 
Skip frequency 
bandwidth 
0.00~P0.04  0.00Hz ○ 
103 
P8.07 
Traverse amplitude  0.0~100.0% 
0.0% O  104 
P8.08 
Jitter frequency  0.0~50.0% 
0.0% O  105 
P8.09 
Rise time of traverse  0.1~3600.0s 
5.0s  O  106 
P8.10 
Fall time of traverse  0.1~3600.0s 
5.0s  O  107 
P8.11 
Auto reset times  0~3 
0  O  108 
P8.12 
Reset interval  0.1~100.0s 
1.0s  O  109 
P8.13 
FDT level  0.00~ P0.04 
50.00Hz O  110 
P8.14 
FDT lag  0.0~100.0% 
5.0% O  111 
P8.15 
Frequency arrive 
detecting range 
0.0~100.0%(maximum frequency) 
0.0% O  112 
P8.16 
Brake threshold 
voltage 
115.0~140.0% 
Depend 
on model
O  113 
P8.17 
Coefficient of rotation 
speed 
0.1~999.9% 
100.0% O  114 
P9 Group: PID Control