Goodrive20-EU series VFD    Function parameters 
49 
Detailed instruction of parameters 
10.000s 
Setting range of P03.02: 0.00Hz – P00.05 
Setting range of P03.05: P03.02 – P00.03 
0 – 8 (corresponds to 0 – 2
8
/10ms) 
Compensation 
coefficient of 
vector control 
electromotion 
slip   
Slip compensation coefficient is used to adjust 
the slip frequency of the vector control and 
improve the speed control accuracy of the 
system. Adjusting the parameter properly can 
control the speed steady-state error.   
Setting range: 50% – 200% 
Compensation 
coefficient of 
vector control 
brake slip   
Current loop 
proportional 
coefficient P 
Note: 
These two parameters adjust the PI adjustment 
parameter of the current loop which affects the 
dynamic response speed and control accuracy 
directly. Generally, users do not need to change 
the default value; 
Only apply to the vector control mode without PG 
0 (P00.00=0). 
Setting range: 0 – 65535 
Current loop 
integral 
coefficient I 
Torque setting 
mode selection 
This parameter is used to enable the torque 
control mode, and set the torque setting means.   
0: Torque control is invalid 
1: Set via keypad(P3.12) 
2: Set via AI1 (100% relative to three times of 
motor current) 
3: Set via AI2 (100% relative to three times of 
motor) (same as above) 
4: Set via AI3 (100% relative to three times of 
motor) (same as above) 
5: Set via pulse frequency HDI (same as above) 
6: Multi-step torque setting (same as above) 
7: Set via MODBUS communication 
8 – 10: Reserved