Goodrive20-EU series VFD    Function parameters 
39 
Detailed instruction of parameters 
Function 
restore 
parameter 
0: No operation   
1: Restore the default value 
2: Clear fault records   
3: Lock all function codes   
Note: The function code will restore to 0 after 
finishing the operation of the selected function 
code. 
Restoring to the default value will cancel the user 
password, please use this function with caution.   
P01 Group    Start-up and stop control 
0: Start-up directly: start from the starting 
frequency P01.01   
1: Start-up after DC braking: start the motor from 
the starting frequency after DC braking (set the 
parameter P01.03 and P01.04). It is suitable in 
the cases where reverse rotation may occur to 
the low inertia load during starting. 
2: Start after speed tracking 1 
3: Start after speed tracking 2 
The direction and speed will be tracked 
automatically for the smoothing starting of 
rotating motors. It suits the application with 
reverse rotation when big load starting. 
Note: This function is only available for the 
VFDs≥4kW 
Starting 
frequency of 
direct start-up 
Starting frequency of direct start-up means the 
original frequency during the VFD starting. See 
P01.02 for detailed information.   
Setting range: 0.00 – 50.00Hz 
Hold time of 
the starting 
frequency 
Set a proper starting frequency to increase the 
torque of the VFD during starting. During the 
retention time of the starting frequency, the 
output frequency of the VFD is the starting 
frequency. And then, the VFD will run from the 
starting frequency to the set frequency. If the set 
frequency is lower than the starting frequency, 
the VFD will stop running and keep in the