Goodrive20-EU series VFD    Function parameters 
67 
Detailed instruction of parameters 
Lower limit of 
AO1 output 
The above function codes define the relative 
relation between the output value and analog 
output. When the output value exceeds the 
range of set maximum or minimum output, it will 
count according to the low-limit or upper-limit 
output. 
When the analog output is current output, 1mA 
equals to 0.5V. 
In different cases, the corresponding analog 
output of 100% of the output value is different. 
Refer to each application for detailed 
information.   
 
Setting range of P06.17: -100.0% – P06.19 
Setting range of P06.18: 0.00V – 10.00V   
Setting range of P06.19: P06.17 – 100.0% 
Setting range of P06.20: 0.00V – 10.00V 
Setting range of P06.21: 0.000s – 10.000s 
Setting range of P06.22:- 100.0% – P06.24 
Setting range of P06.23: 0.00V – 10.00V 
Setting range of P06.24: P06.22 – 100.0% 
Setting range of P06.25: 0.00V – 10.00V 
Setting range of P06.26: 0.000s – 10.000s 
Corresponding 
AO1 output to 
the lower limit 
Upper limit of 
AO1 output 
Corresponding 
AO1 output of 
the upper limit 
Lower limit of 
AO2 output 
Corresponding 
AO2 output to 
the lower limit 
Upper limit of 
AO2 output 
Corresponding 
AO2 output to 
the upper limit 
P07 Group    Human-Machine Interface 
0 – 65535 
The password protection will be valid when 
setting any non-zero number. 
00000: Clear the previous user's password, and 
make the password protection invalid.   
After the user's password becomes valid, if the 
password is incorrect, users cannot enter the 
parameter menu. Only correct password can 
make the user check or modify the parameters.