Goodrive200 inverters                                                                                    Function codes   
127 
Function 
code 
Name 
Detailed instruction of parameters 
Default 
value
of 
communic
ation 
overtime 
When the function code is set as 0.0, the 
communication overtime parameter is invalid.   
When the function code is set as non-zero, if the 
interval time between two communications 
exceeds the communication overtime, the 
system will report “485 communication faults” 
(CE). 
Generally, set it as invalid; set the parameter in 
the continuous communication to monitor the 
communication state. 
P14.05
Transmissi
on fault 
processing
0:Alarm and stop freely   
1:No alarm and continue to run   
2:No alarm and stop according to the stop means
(only under the communication control) 
3:No alarm and stop according to the stop means
(under all control modes) 
0  ○ 
P14.06
LED ones: 
0: Operation with response: the drive will respond 
to all reading and writing commands of the upper 
monitor.   
1:Operation without response;The drive only 
responds to the reading command other than the 
writing command of the drive. The 
communication efficiency can be increased by 
this method.   
LED tens: 
0: Communication encrypting valid 
1: Communication encrypting invalid 
0x00  ○ 