Goodrive200 inverters                                                                                        Fault tracking       
Fault type  Possible cause  What to do 
OUt1  IGBT Ph-U fault
 The acceleration is too 
fast 
 IGBT module fault 
 Misaction caused by 
interference 
 The connection of the 
driving wires is not good, 
 Grounding is not properly
 Increase Acc time 
 Change the power unit 
 Check the driving wires 
 Inspect external 
equipment and eliminate 
interference 
OUt2  IGBT Ph-V fault
OC1 
Over-current when 
acceleration 
 The acceleration or 
deceleration is too fast 
 The voltage of the grid is 
too low 
 The power of the inverter 
is too low 
 The load transients or is 
abnormal 
 The grounding is short 
circuited or the output is 
phase loss 
 There is strong external 
interference 
 The overvoltage stall 
protection is not open 
 Increase the ACC time 
 Check the input power 
 Select the inverter with a 
larger power   
 Check if the load is short 
circuited (the grounding 
short circuited or the wire 
short circuited) or the 
rotation is not smooth 
 Check the output 
configuration.   
 Check if there is strong 
interference 
 Check the setting of 
relative function codes 
OC2 
Over-current when 
deceleration 
OC3 
Over-current when 
constant speed 
running   
OV1 
Over-voltage 
when acceleration
 The input voltage is 
abnormal 
 There is large energy 
feedback 
 No braking components 
 Braking energy is not open
 Check the input power 
 Check if the DEC time of 
the load is too short or the 
inverter starts during the 
rotation of the motor or it 
needs to add the dynamic 
braking components 
 Install the braking 
components 
 Check the setting of 
relative function codes 
OV2 
Over-voltage 
when deceleration
OV3 
Over-voltage 
when constant 
speed running 
UV 
DC bus 
Under-voltage 
 The voltage of the power 
supply is too low 
 The overvoltage stall 
protection is not open 
 Check the input power of 
the supply line   
 Check the setting of 
relative function codes