Goodrive300 Series VFD    Function parameters 
120 
Detailed instruction of parameters 
Temporarily 
variable 1 for 
PZD sending   
Fault tiem of 
DP 
communicatio
n overtime   
0.0 (invalid),0.1–60.0s 
When  this  function  code  is  set  as  0.0,  this 
function is invalid.   
When the function code is set as nonzero value, if 
the  internal  time  between  two  adjent 
communications  exceeds  the  communication 
overtime,  the  system  will  report  "PROFIBUS 
communication fault" (E-DP). 
Fault tiem of 
CANopen 
communicatio
n overtime 
0.0(invalid), 0.1–60.0s 
When  this  function  code  is  set  as  0.0,  this 
function is invalid.   
When the function code is set as nonzero value, if 
the  internal  time  between  two  adjent 
communication  exceeds  the  communication 
overtime,  the  system  will  report  "CANopen 
communication fault" (E-CAN). 
0: 1000k 
1: 800k 
2: 500k 
3: 250k 
4: 125k 
5: 100k 
6: 50k 
7: 20k   
P16 Group    Ethernet function   
Speed setting 
of the Ethernet 
communicatio
n 
0: Self-adapting 
1: 100M full duplex 
2: 100M semiduplex 
3: 10M full duplex 
4: 10M semiduplex   
The  function  code  is  used  to  set  the  Ethernet 
communication speed.   
0–255 
Set the IP address of Ethernet communication.