Goodrive300 Series VFD    Function parameters 
117 
Detailed instruction of parameters 
the  VFD  must  be  the  same.  Otherwise,  the 
communication  is  not  applied.  The  bigger  the 
baud rate, the quicker the communication speed. 
The data format between the upper monitor and 
the  VFD  must  be  the  same.  Otherwise,  the 
communication is not applied. 
0: No check (N,8,1) for RTU 
1: Even check (E,8,1) for RTU 
2: Odd check (O,8,1) for RTU 
3: No check (N,8,2) for RTU 
4: Even check (E,8,2) for RTU 
5: Odd check(O,8,2) for RTU 
0–200ms 
The interval time when the drive receives the data 
and  sent  it  to  the  upper  monitor.  If  the  answer 
delay is shorter than the system processing time, 
then  the  answer  delay  time  is  the  system 
processing  time,  if  the  answer  delay  is  longer 
than the  system  processing time, then  after  the 
system  deal  with  the  data,  waits  until  achieving 
the  answer  delay  time  to  send  the  data  to  the 
upper monitor.   
Fault time of 
communicatio
n overtime   
0.0(invalid), 0.1–60.0s 
When  the  function  code  is  set  as  0.0,  the 
communication overtime parameter is invalid.   
When the function code is set as non-zero, if the 
interval  time  between  two  communications 
exceeds the communication overtime, the system 
will report "485 communication faults" (CE). 
Generally, set  it  as  invalid; set  the parameter in 
the  continuous  communication  to  monitor  the 
communication state. 
Transmission 
fault 
processing 
0: Alarm and stop freely   
1: No alarm and continue to run   
2: No alarm and stop according to the stop mode 
(only under the communication control) 
3: No alarm and stop according to the stop mode 
(under all control modes)