Goodrive300 Series VFD    Function parameters 
118 
Detailed instruction of parameters 
0x00–0x11 
LED ones: 
0: Write with response: the VFD will respond to all 
reading  and  writing  commands  of  the  upper 
monitor.   
1: Write without response: the VFD only responds 
to  the  reading  command  other  than  the  writing 
command  of  the  drive.  The  communication 
efficiency can be increased by this method.   
LED tens: 
0: Communication encrypting is invalid 
1: Communication encrypting is valid 
P15 Group    PROFIBUS/CANopen function 
0: PROFIBUS 
1: CANopen 
Select communication protocol 
0–127 
This  function  code  is  used  to  designate  the 
address of the VFD.   
Note: 0 is the broadcast address, when set it as 
broadcast  address,  only  receive  the  radio 
command  of  the  upper  monitor  other  than 
answering the upper monitor. 
0: Invalid 
1: Setting frequency (0–Fmax(unit:0.01Hz)) 
2:  PID  reference,  range  (0–1000,  1000 
corresponds to 100.0%) 
3:  PID  feedback,  range  (0–1000,  1000 
corresponds to 100.0%) 
4: Torque setting (-3000–3000,1000 corresponds 
to 100.0% the rated current of the motor) 
5:  Upper frequency  of forward rotation (0–Fmax 
unit:0.01Hz)) 
6:  Upper  frequency  of  reverse  rotation 
(0–Fmax(unit:0.01Hz)) 
7: Electromotion torque upper limit (0–3000,1000 
corresponds to 100.0%of the rated current of the