Goodrive300 Series VFD Function parameters
105
Detailed instruction of parameters
Setting range: -0x0000–0xFFFF
0: Restart from the first step; stop during running
(cause by the stop command, fault or power loss),
run from the first stage after restart.
1: Continue to run from the stop frequency; stop
during running(cause by stop command and
fault), the VFD will record the running time
automatically, enter into the stage after restart
and keep the remaining running at the setting
frequency.
0: Seconds; the running time of all steps is
counted by second
1: Minutes; the running time of all steps is
counted by minute
P11 Group Protective parameters
0x00–0x11
LED ones:
0: Input phase loss protection disable
1: Input phase loss protection enable
LED tens:
0: Output phase loss protection disable
1: Output phase loss protection enable
Frequency-de
creasing at
sudden power
loss
Frequency
decreasing
ratio at sudden
power loss
Setting range: 0.00Hz/s–P00.03 (Max. frequency)
After the power loss of the grid, the bus voltage
drops to the sudden frequency-decreasing point,
the VFD begin to decrease the running frequency
at P11.02, to make the VFD generate power
again. The returning power can maintain the bus
voltage to ensure a rated running of the VFD until
the recovery of power.
Frequency-decrea
sing point at