Goodrive300 Series VFD Function parameters
106
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
sudden power loss
Note:
1. Adjust the parameter properly to avoid the
stopping caused by VFD protection during the
switching of the grid.
2. Disable input phase loss protection to enable
this function.
P11.03
Overvoltage
stall protection
0:Disable
1: Enable
DC bus
voltage V
Overvoltage
small point
Output
frequency
Time t
Time t
1
P11.04
Voltage
protection of
overvoltage
stall
120150%(standard bus voltage)( 380V)
136%
120150%(standard bus voltage)( 500V)
132%
120150%(standard bus voltage)(660V)
120%
P11.05
Current limit
action
selection
The actual increasing ratio of motor speed is
lower than the ratio of output frequency because
of the big load during ACC running. It is
necessary to take measures to avoid overcurrent
fault and the VFD trips.
Ones: current limit:
0: Invalid
1: Valid
Tens: overload alarm of hardware current limit
(for factory commissioning)
0: Valid
1: Invalid
01