Goodrive300 Series VFD Function parameters
77
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
of AI3
Setting range of P05.37: 0.00VP05.39
Setting range of P05.38: -100.0%100.0%
Setting range of P05.39: P05.3710.00V
Setting range of P05.40: -100.0%100.0%
Setting range of P05.41: 0.000s10.000s
Setting range of P05.42: -10.00VP05.44
Setting range of P05.43: -100.0%100.0%
Setting range of P05.44: P05.42P05.46
Setting range of P05.45: -100.0%100.0%
Setting range of P05.46: P05.4410.00V
Setting range of P05.47: -100.0%100.0%
Setting range of P05.48: 0.000s10.000s
P05.45
Corresponding
middle setting
of AI3
0.0%
P05.46
Upper limit of
AI3
10.00V
P05.47
Corresponding
setting of
the upper limit
of AI3
100.0%
P05.48
AI3 input filter
time
0.100s
P05.49
HDI
high-speed
pulse input
function
selection
The function selection when HDI terminals is
high-speed pulse input
0: Frequency setting input, frequency setting
source
1: Counter input, high-speed pulse counter input
terminals
2: Length counting input, length counter input
terminals
0
P05.50
Lower limit
frequency of
HDI
0.000kHzP05.52
0.000
kHz
P05.51
Corresponding
setting of HDI
low frequency
setting
-100.0%100.0%
0.0%
P05.52
Upper limit
frequency of
HDI
P05.5050.000kHz
50.000
kHz
P05.53
Corresponding
setting of
upper limit
frequency of
HDI
-100.0%100.0%
100.0%
P05.54
HDI frequency
input filter time
0.000s10.000s
0.010s