Goodrive300 Series VFD Function parameters
78
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P06 Group Output terminals
P06.00
HDO output
The function selection of the high-speed pulse
output terminals.
0: Open collector high speed pulse output: The
Max.pulse frequency is 50.0kHz. See
P06.27P06.31 for detailed information of the
related functions.
1: Open collector output. See P06.02 for detailed
information of the related functions.
0
P06.01
Y1 output
0: Invalid
1: In operation
2: Forward rotation operation
3: Reverse rotation operation
4: Jogging operation
5: The VFD fault
6: Frequency degree test FDT1
7: Frequency degree test FDT2
8: Frequency arrival
9: Zero speed running
10: Upper limit frequency arrival
11: Lower limit frequency arrival
12: Ready for operation
13: Pre-magnetizing
14: Overload pre-alarm
15: Underload pre-alarm
16: Completion of simple PLC stage
17: Completion of simple PLC cycle
18: Set count value reached
19: Specified count value reached
20: External fault valid
21: Length arrival
22: Running time arrival
23: Modbus communication virtual terminals
output
24: PROFIBUS/CANopen communication virtual
terminals output
25: Ethernet communication virtual terminals
0
P06.02
HDO output
0
P06.03
Relay RO1
output
1
P06.04
Relay RO2
output
5