Goodrive300 Series VFD Function parameters
82
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Please remember all users’ passwords.
Retreat editing state of the function codes and the
password protection will become valid in minute.
If the valid password is available, press
PRG/ESC to enter into the editing state of the
function codes, and then "0.0.0.0.0" will be
displayed. Unless input right password, the
operator cannot enter into it.
Note: Restoring to the default value can clear the
password, use it with caution.
P07.01
Parameter
copy
The function code determines the manner of
parameters copy.
0: No operation
1: Upload the local function parameter to the
keypad
2: Download the keypad function parameter to
local address (including the motor parameters)
3: Download the keypad function parameter to
local address (excluding the motor parameter of
P02 and P12 group)
4: Download the keypad function parameters to
local address (only for the motor parameter of
P02 and P12 group)
Note: After completing the 14 operations, the
parameter will come back to 0 automatically; the
function of upload and download excludes the
factory parameters of P29.
0
P07.02
QUICK/JOG
function
selection
0: No function
1: Jogging. Press QUICK/JOG to begin the
jogging running.
2: Shift the display state by the shifting key. Press
QUICK/JOG to shift the displayed function code
from right to left.
3: Shift between forward rotations and reverse
rotations. Press QUICK/JOG to shift the direction
of the frequency commands. This function is only
valid in the keypad commands channels.
4: Clear UP/DOWN settings. Press QUICK/JOG
1