Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-161-
Function
code
Name
Description
Default
value
Modify
P07.10
Linear speed
display
coefficient
0.1999.9%
Linear speed=mechanical speed×P07.10
1.0%
P07.11
Temperature of
rectifier bridge
module
-20.0120.0°C
/
P07.12
Temperature of
inverter module
-20.0120.0°C
/
P07.13
Software version
of control board
1.00655.35
/
P07.14
Accumulated
running time
065535h
/
P07.15
High bit of VFD
power
consumption
Display the power consumption of the VFD.
VFD power consumption=P07.15×1000+P07.16
Setting range of P07.15: 065535 kWh (×1000)
Setting range of P07.16: 0.0999.9 kWh
/
P07.16
Low bit of VFD
power
consumption
/
P07.17
Reserved
/
/
P07.18
Rated power of
VFD
0.43000.0kW
/
P07.19
Rated voltage of
VFD
501200V
/
P07.20
Rated current of
VFD
0.16000.0A
/
P07.21
Factory barcode
1
0x00000xFFFF
/
P07.22
Factory barcode
2
0x00000xFFFF
/
P07.23
Factory barcode
3
0x00000xFFFF
/
P07.24
Factory barcode
4
0x00000xFFFF
/
P07.25
Factory barcode
5
0x00000xFFFF
/
P07.26
Factory barcode
6
0x00000xFFFF
/
P07.27
Present fault
type
0: No fault
1: Inverter unit U phase protection (OUt1)
2: Inverter unit V phase protection (OUt2)
3: Inverter unit W phase protection (OUt3)
4: Overcurrent during acceleration (OC1)
5: Overcurrent during deceleration (OC2)
6: Overcurrent during constant speed (OC3)
/
P07.28
Last fault type
/
P07.29
2nd-last fault
type
/
P07.30
3rd-last fault
type
/