Goodrive350 series high-performance multi-function inverter Chapter 6
-187-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
error processing
1: Do not alarm and continue running
2: Do not alarm and stop as per the stop mode
(under communication control mode only)
3: Do not alarm and stop as per the stop mode
(under all control modes)
P14.06
Communication
processing action
0x000x11
Ones:
0: Write operation has response
1: Write operation has no response
Tens:
0: Communication password protection is invalid
1: Communication password protection is valid
0x00
P14.07
P14.24
Reserved
variables
065535
0
P15 group Functions of communication extension card 1 (see the operation manual of
communication extension card for details)
P16 group Functions of communication extension card 2
P16.00
P16.23
See the operation manual of communication extension card for details
P16.24
Identification
time for the
extension card in
card slot 1
0.0600.0s
If it is set to 0.0, identification fault will not be
detected
0.0
600.00
0.0
P16.25
Identification
time for the
extension card in
card slot 2
0.0600.0s
If it is set to 0.0, offline fault will not be detected
0.0
600.00
0.0
P16.26
Identification
time for the
extension card in
card slot 3
0.0600.0s
If it is set to 0.0, offline fault will not be detected
/
/
P16.27
Communication
timeout period of
extension card in
card slot 1
0.0600.0s
If it is set to 0.0, offline fault will not be detected
/
/
P16.28
Communication
timeout period of
extension card in
0.0600.0s
If it is set to 0.0, offline fault will not be detected
/
/