Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-54-
Detailed instruction of parameters
Setting range: 0.0~3600.0s
Shifting
between
FWD/REV
rotation
Set the threshold point of the inverter:
0: Switch after zero frequency
1: Switch after the starting frequency
2: Switch after the speed reaches P01.15 and delays
for P01.24
Detection of
stopping
speed
0: Detect according to speed setting (no stopping
delay)
1: Detect according to speed feedback (only valid for
vector control)
Detection
time of
feedback
speed
If set P01.16 to 1, the feedback frequency is less than
or equal to P01.15 and detect in the set time of
P01.17, the inverter will stop; otherwise, the inverter
will stop after the set time of P01.17.
Setting range: 0.00~100.00s (only valid when
P01.16=1)