Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-56-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
frequency is above the lower limit one.
Setting range: 0.0~3600.0s (valid when P01.19=2)
P01.21
Restart after
power off
This function can enable the inverter to start or not
after power off and then power on.
0: Disable
1: Enable, if the starting need is met, the inverter will
run automatically after waiting for the time defined by
P01.22.
0
P01.22
The waiting
time of
restart after
power off
The function determines the waiting time before the
automatic running of the inverter when powering off
and then powering on.
Setting range: 0.0~3600.0s (valid when P01.21=1)
1.0s
P01.23
Start delay
time
The function determines the brake release after the
running command is given, and the inverter is in a
stand-by state and waits for the delay time set by
P01.23.
Setting range: 0.0~60.0s
0.0s
P01.24
Delay time
of stop
speed
Setting range: 0.0~100.0s
0.0s
P01.25
0Hz output
selection
Select the output mode at 0Hz.
0: Output without voltage
1: Output with voltage
0