Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-69-
Detailed instruction of parameters
overcurrent may occur. These phenomena can be
canceled by adjusting this parameter.
The setting range of P04.23: 0~100
The setting range of P04.24: 0~100
The setting range of P04.25: 0.00Hz~P00.03 (the
Max. frequency)
Vibration
control factor
at high
frequency of
motor 2
Vibration
control
threshold of
motor 2
0: No operation
1: Automatic energy-saving operation
Motors will automatically adjust the output voltage to
save energy at light loads.
Select the output setting channel at V/F curve
separation.
0: Keypad: the output voltage is determined by
P04.28.
1: AI1
2: AI2
3: AI3
4: HDI
5: Multi-step speed
6: Reserved
7: Modbus communication
8~10: Reserved
Note: 100% corresponds to the rated voltage of
the motor.
The function code is the voltage displaying when the
voltage is set through keypad.
The setting range: 0.0%~100.0%
Voltage increasing time is the time when the inverter