Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-70-
Detailed instruction of parameters
accelerates from the minimum output voltage to the
maximum output voltage.
Voltage decreasing time is the time when the inverter
decelerates from the maximum output voltage to the
minimum output voltage.
The setting range: 0.0~3600.0s
Set the upper and low limit of the output voltage.
The setting range of P04.31: P04.32~100.0% (the
rated voltage of the motor)
The setting range of P04.32: 0.0%~P04.31
Weakening
coefficient in
constant
power zone
The function is used to adjust the output voltage of
inverter in SVPWM mode in weak magnetic.
Note: Invalid in constant-torque mode
The setting range of P04.33: 1.00~1.30
P05 Group Input terminals
0: High-speed pulse input. See P05.49~P05.54
1: Digital input. See P05.09
S1 terminal
function
selection
0: No function
1: Forward rotation operation
2: Reverse rotation operation
3: 3-wire control operation (SIn)
4: Forward jogging