Goodrive35 Series Closed-loop Vector Control VFD Function parameters
66
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modif
y
P03.20
Keypad setting of
electromotion torque
The function code is used to set the limit of the
torque.
Setting range: 0.0300.0% (motor rated current)
180.0%
P03.21
Keypad setting of
brake torque
180.0%
P03.22
Weakening
coefficient in
constant power zone
The usage of AM in weakening control.
T
f
0.1
Flux-weakening
coefficient of motor
1.0
2.0
Min. flux-weakening limit of motor
Function code P03.22 and P03.23 are effective at
constant power. The motor will enter into the
weakening state when the motor runs at rated
speed. Change the weakening curve by modifying
the weakening control coefficient. The bigger the
weakening control coefficient is, the steeper the
weak curve is.
The setting range of P03.22: 0.102.00
The setting range of P03.23: 5%50%
1.00
P03.23
Lowest weakening
point in constant
power zone
20%
P03.24
Max voltage limit
P03.24 set the max voltage of the VFD, which is
dependent on the site situation.
The setting range: 0.0120.0%
100.0%
P03.25
Pre-exciting time
Preactivate the motor when the VFD starts up. Build
up a magnetic field inside the VFD to improve the
torque performance during the starting process.
The setting time: 0.00010.000s
0.000 s
P03.26
Weak proportional
gain
The response characteristic of the flux weakening
controller is relative to P03.26 and P03.27. It can be
adjusted properly.
Setting range: 08000
1200
P03.27
Integral gain of the
flux weakening
1200
P03.28
Control mode of flux
weakening
0x0000x112
Ones: Control mode selection
0: Mode 0;
1: Mode 1;
0x000