Goodrive35 Series Closed-loop Vector Control VFD Function parameters
90
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modif
y
Setting range: 0.00 HzP00.03 (max. output
frequency)
P08.15
Overvoltage stall
modulator gain
Setting range: 0.01000.0
12.0
P08.16
ASR differential gain
Setting range: 0.0010.00s
0.00 s
P08.17
Max torque of inertia
compensation
Limit the max. inertia compensation torque to
prevent the inertia compensation torque from being
too large.
Setting range: 0.0150.0% (rated torque of the
motor)
20.0%
P08.18
Inertia compensation
filter times
Filter times of inertia compensation torque is used to
smooth the inertia compensation torque.
Setting range: 010
7
P08.19
High-frequency ACR
proportional
coefficient
In the closed-loop vector control mode (P00.00=3),
when the running frequency is lower than the ACR
high frequency switching point (P08.21), the ACR PI
parameters are P03.09 and P03.10; and when the
running frequency is higher than the ACR high
frequency switching point, the ACR PI parameters
are P08.19 and P08.20.
Setting range of P08.19: 020000
Setting range of P08.20: 020000
Setting range of P08.21: 0.0100.0% (relative max
frequency)
1000
P08.20
High-frequency ACR
integral coefficient
1000
P08.21
ACR high frequency
switching point
100.0%
P08.22
Inertia identification
torque
Because of the friction, it is necessary to set
identification torque for normal inertia identification.
0.0100.0% (rated torque of the motor)
10.0%
P08.23
Inertia identification
0: No operation
1: Starting identification: press "RUN" to enter into
the program after starting identification until display
"-END-"; the identified system inertia is saved in
P08.24.
0
P08.24
System inertia
The identified system inertia can be set manually
when the system inertia is known. The displayed
system inertia may be less than 0.001kgm
2
for the
motors below 1 kW.
Setting range: 0.00030.000 kgm
2
0.000
kgm
2