Goodrive35 Series Closed-loop Vector Control VFD  Function parameters 
111 
Detailed instruction of parameters 
The  smaller  K  is,  the  greater  M  is,  and  the  more 
likely protection is implemented. 
When M=116%, protection is performed after motor 
overload lasts for 1 hour; when M=150%, protection 
is  performed  after  motor  overload  lasts  for  12 
minutes;  when  M=180%,  protection  is  performed 
after  motor  overload  lasts  for  5  minutes;  when 
M=200%,  protection  is  performed  after  motor 
overload lasts for 60 seconds; and when M≥  400%, 
protection is performed immediately. 
1
5
12
60
116%
200%
Time (min)
Motor overload 
multiple
150% 180%
 
Setting range: 20.0%–120.0% 
Parameter display of 
motor 2 
0:  Display  according  to  the  motor  type:  only  the 
parameters  relative  to  the  current  motor  type  are 
displayed for the convenient for the customers in this 
mode.   
1:  All parameters are  displayed: all parameters are 
displayed in this mode. 
Reduction coefficient 
of source current 
0.0–100.0% (rated current of the motor) 
0: No test 
1: High-frequency superposition (reserved) 
2: Pulse superposition (reserved) 
Source  current  is  the  positioning  current  of  the 
magnetic  pole  position.  Source  current  1  is  valid 
under  the  frequency  point  of  current  shifting. 
Increasing the value can raise the starting torque. 
Setting  range:  0.0%–100.0%  (rated  current  of  the