142
Function
code
Name
Detailed instruction of parameters
Default
value
8: Ethernet communication setting
upper-limit frequency (the same as above)
Note: Setting method 08, 100%
corresponds to the maximum frequency.
P03.15
Upper frequency of reverse
rotation in vector control
0: Keypad (P03.17)
18: The same as P03.14
P03.16
Keypad setting for upper
frequency of forward rotation
Setting range: 0.00 HzP00.03 (max.
output frequency)
50.00 Hz
P03.17
Keypad setting for upper
frequency of reverse rotation
50.00 Hz
P03.18
Upper electromotion torque
source
0: Keypad setting upper-limit frequency
(P03.20)
1: AI1
2: AI2
3: AI3
4: HDI
5: Modbus communication
6: PROFIBUS/CANopen communication
7: Ethernet communication
Note: Set mode 17, 100% corresponds to
three times of the motor current.
P03.19
Upper brake torque source
0: Keypad (P03.21)
17: The same as P03.18
P03.20
Keypad setting of
electromotion torque
0.0300.0% (rated current of the motor)
180.0%
P03.21
Keypad setting of brake torque
180.0%
P03.22
Weakening coefficient in
constant power zone
0.012.00
1.00
P03.23
Lowest weakening point in
constant power zone
5%50%
10%
P03.24
Max voltage limit
0.0120.0%
100.0%
P03.25
Pre-exciting time
0.00010.000 s
0.0 s
P03.26
Weak proportional gain
08000
1200
P03.27
Integral gain of the flux
weakening
08000
1200
P03.28
Control mode of the flux
weakening
0x0000x112
Ones: Control mode selection