Goodrive35 Series Closed-loop Vector Control VFD Installation guide
28
Terminalname
Description
current output is depended on the jumper. AO1 is switched by J1
and AO2 is switched by J2
2. Deviation±1%, 25°C
AO2
Terminalname
Description
RO1A
RO1 relay output; RO1A is NO, RO1B is NC, RO1C is common
port
Contact capacity: 3A/AC250V, 1A/DC30V
RO1B
RO1C
RO2A
RO2 relay output; RO2A is NO, RO2B is NC, RO2C is common
port
Contact capacity: 3A/AC250V, 1A/DC30V
RO2B
RO2C
Terminalname
Description
HDO
1. Switch capacity: 200mA/30V;
2. Range of output frequency: 050kHz
COM
Common port of +24V
CME
Common port of open collector output
Y
1. Switch capacity: 200mA/30V;
2. Range of output frequency: 01kHz
485+
For 485 communication port, 485 differential signal port and
standard 485 communication interfaces, use twisted pairs or
shielded cables.
485-
Terminalname
Description
PE
Grounding terminal
PW
Provide input digital working power from external to internal;