Goodrive20-EU series VFD Fault tracking
102
Item to be checked
Details
Check mode
Criterion
Conductor lead
Ensure that there is no
distortion or
color-changing of the
conductors caused by
overheating.
Visual examination
NA
Ensure that there are no
crackles or
color-changing of the
protective layers.
Visual examination
NA
Terminals seat
Ensure that there is no
damage
Visual examination
NA
Filter capacitors
Ensure that there is no
weeping,
color-changing, crackles
and cassis expansion.
Visual examination
NA
Ensure the safety valve
is in the right place.
Estimate the usage
time according to
the maintenance or
measure the static
capacity.
NA
If necessary, measure
the static capacity.
Measure the
capacity by
instruments.
The static capacity
is above or equal
to the original
value *0.85.
Resistors
Ensure whether there is
replacement and
splitting caused by
overheating.
Smelling and visual
examination
NA
Ensure that there is no
offline.
Visual examination
or remove one
ending to coagulate
or measure with
multimeters
The resistors are
in ±10% of the
standard value.
Transformers
and reactors
Ensure there is no
abnormal vibration,
noise and smelling,
Hearing, smelling
and visual
examination
NA
Electromagnetic
contactor and
relay
Ensure whether there is
vibration noise in the
workrooms.
Hearing
NA

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive20-EU VFD Series and is the answer not in the manual?

INVT Goodrive20-EU VFD Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive20-EU VFD Series
CategoryDC Drives
LanguageEnglish

Related product manuals