Goodrive20-EU series VFD Function parameters
69
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
2: Lock part of the keys (lock PRG/ESC key
only)
P07.03
QUICK/JOG
the shifting
sequence of
running
command
When P07.02=6, set the shifting sequence of
running command channels.
0: Keypad control→terminals control
→communication control
1: Keypad control←→terminals control
2: Keypad control←→communication control
3: Terminals control←→communication control
0
P07.04
STOP/RST
stop function
Select the stop function by STOP/RST.
STOP/RST is effective in any state for the
keypad reset.
0: Only valid for the keypad control
1: Both valid for keypad and terminals control
2: Both valid for keypad and communication
control
3: Valid for all control modes
0
P07.05
Displayed
parameters 1
of running state
0x0000 0xFFFF
BIT0: running frequency (Hz on)
BIT1: set frequency (Hz flickering)
BIT2: bus voltage (Hz on)
BIT3: output voltage (V on)
BIT4: output current (A on)
BIT5: running rotation speed (rpm on)
BIT6: output power (% on)
BIT7: output torque (% on)
BIT8: PID reference (% flickering)
BIT9: PID feedback value (% on)
BIT10: input terminals state
BIT11: output terminals state
BIT12: torque set value (% on)
BIT13: pulse counter value
BIT14: reserved
BIT15: PLC and the current step of multi-step
speed
0x03FF