Goodrive300-01A series VFD for air compressor Wiring instruction
-15-
Analog temperature
signal 1
1. Resolution rate: 1°C
2. Range: -20°C –150°C
3. Detection precision: 3°C
Analog temperature
signal 2
1. Input range: current/voltage is
optional, 0–20mA/0–10V; of which P1 is
switched via J7 and P2 via J8
2. Input impedance: 20kΩ during voltage
input; 500Ω during current input
3. Resolution rate: 5mV (minimum value)
4. Error: ±1%, 25°C
1. Output range: 0–10V voltage or
0–20mA current; voltage or current
output is set by the jumper; AO1 is
switched via J2.
2. Error: ±1%, 25°C
1. Internal impedance: 3.3kΩ
2. 12–30V voltage input is acceptable
3. Max. input frequency: 1kHz
485 communication terminal, adopting
the Modbus RTU protocol
PE: When selecting PE through J10, it
can be used as the connecting terminal
of 485 communication shielded cable;
CGND: When selecting CGND through
J10, it can be used as the connecting
terminal of 485 communication shielded
cable
1. Contact capacity: 3A/AC250V,
1A/DC30V
2. Cannot be used as high-frequency
switch output
Note: RO1 port of single-VFD integrated
machine is connected to solenoid coil
port by default.
Public contact of relay 1
Public contact of relay 2
Public contact of relay 3