Goodrive300-01A series VFD for air compressor Function code description
-29-
Function
code
Name
Parameter description
Default
value
Modify
6: Set via multi-step speed running
7: Set via PID control
8: Set via Modbus communication
911: Reserved
P00.08
Reference object of B
frequency command
0: Max. output frequency
1: A frequency command
0
P00.09
Combination mode of
setting source
0: A
1: B
2: (A+B)
3: (A-B)
4: Max. (A, B)
5: Min. (A, B)
0
P00.10
Frequency set through
keypad
0.00 HzP00.03 (max. frequency)
50.00Hz
P00.11
Acceleration time 1
0.03600.0s
Depend
on model
P00.12
Deceleration time 1
0.03600.0s
Depend
on model
P00.13
Running direction
0: Run by default direction
1: Run by reverse direction
2: Reverse running prohibited
2
P00.14
Carrier frequency
setting
1.015.0kHz
Depend
on model
P00.15
Motor parameter
autotuning
0: No operation
1: Rotary autotuning
2: Static autotuning 1 (comprehensive
autotuning)
3: Static autotuning 2 (partial autotuning)
0
P00.16
AVR function selection
0: Invalid
1: Valid during the whole time
1
P00.17
VFD type
0: G type
1: P type
0
P00.18
Function parameter
restoration
0: No operation
1: Restore to default value
2: Clear fault history
Note: When restoring to default values, the
motor parameters in P02 group will stay in
current value; in addition, P18.04, P18.28,
P18.29, P18.32, P18.33, P18.38 in P18 group
0