Goodrive300 Series VFD Fault tracking
191
Reset the rotating motor
The voltage of the grid is too
low.
The load is too heavy.
The motor power is too small
Avoid the restarting after stopping.
Check the power of the grid
Select a VFD with bigger power.
Select a proper motor.
Phase loss or fluctuation of
input R,S,T
Check input power
Check installation distribution
U,V,W phase loss input (or
serious asymmetrical three
phase of the load)
Check the output distribution
Check the motor and cable
Rectifier
module
overheated
Air duct jam or fan damage
Ambient temperature is too
high.
The time of overload running
is too long.
Dredge the vent duct or replace
the fan
Lower the ambient temperature
Inverter
module
overheated
SI external fault input
terminals action
Check the external device input
The baud rate setting is
incorrect.
Fault occurs to the
communication wiring.
The communication address is
wrong.
There is strong interference to
the communication.
Set proper baud rate
Check the communication
connection distribution
Set proper communication
address.
Change or replace the connection
distribution or improve the
anti-interference capability.
The connection of the control
board is not good
Hall components are broken
The modifying circuit is
abnormal.
Check the connector and repatch
Change the Hall
Change the main control panel
The motor capacity does not
comply with the VFD capability
The rated parameter of the
motor does not set correctly.
The offset between the
Change the VFD mode
Set the ratedparameter according
to the motor name plate
Empty the motor load and
reindentify