Goodrive300 Series VFD Extension card
234
1
Repeat
er
2 3 30 31
1 2 30 31
Repeat
er
Terminal
A.2.6.4 Transmission rate and maximum distance
Maximum length of cable depends on the transmission rate. The Table below shows the relationship
between transmission rate and distance.
Transmission rate (kbps)
A-wire (m)
B-wire (m)
9.6
1200
1200
19.2
1200
1200
93.75
1200
1200
187.5
1000
600
500
400
200
1500
200
-----
12000
100
-----
Transmission line parameters:
Transmission rate (kbps)
A-wire (m)
B-wire (m)
Impedance (Ω)
135165
100130
Capacitance per unit length(pF/m)
< 30
< 60
Loop Resistance (Ω/km)
110
--------
Core wire diameter (mm)
0.64
> 0.53
Line-core cross-section (mm
2
)
> 0.34
> 0.22
Besides shielding twisted-pair copper wires, PROFIBUS can also use optical fiber for transmission in
an electromagnetic interference environment to increase the high-speed transmission distance there
are two kinds of fiber optical conductors, one is low-cost plastic fiber conductor, used distance is less
than 50 meters, the other is glass fiber conductor, and used distance is less than 1 kM.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive300 Series and is the answer not in the manual?

INVT Goodrive300 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals