C. Modes and Adjustments
1. Auto
a. This is the normal operaonal mode of the M820
controller.
b. The controller allows full operaon and monitoring of both
pH and ORP levels.
c. No funcon pushbuons are operaonal in this mode.
d. The red funcon LED next to Auto is illuminated.
e. pH and ORP digital displays monitor the sensor input
levels.
2. pH standby
Note: While in this mode, the green pH standby LED will
illuminate, both the pH and ORP digital displays will show
dashes, and all Auto funcons will be disabled. When a funcon
pushbuon is pressed, the corresponding digital display will show
the funcon. Use the Up or Down arrow buons to the le to
increase or decrease the funcon value.
a. Set Level
1. Default: 7.4 pH
2. Selectable range: 7.0 – 8.0 pH (in 0.1 increments)
b. Dose Time
1. Default: Timed dose of 10-second pH feed relay
energized and 5 minutes pH feed relay de-energized.
In the med dose cycle mode, the dose LED will ash
while dosing and illuminate steadily during the delay
poron of the med cycle. In connuous dose mode,
the dose LED will ash while dosing, and dosing will
connue unl pH is 0.2 below (or above if feeding base)
Set Level.
2. Selectable range: OFF, CON (connuous), and Timed
(10 – 900 seconds ON)
17
M820 pH/Dual ORP Controller Owner’s Manual