c. Delay Time
1. Default: Delay me of 5 minutes between feed cycles
(med feed only). Aer dose me, the controller will
wait (delay) for the specied minutes before checking
the current level and dosing again if necessary.
2. Selectable range: 1 - 99 minutes.
d. Over Timer
1. Default: ON. The Over Timer does not automacally
reset. It must be reset by pressing the Mode buon to
cycle through the Standby mode and back to the Auto
mode.
2. The Over Timer is interlocked with the Dose Time
selecon.
a. If the Dose Time is set to a med cycle, the Over
Timer will count med feed cycles. Every me the
set level is reached the me will reset its count. If
the preset cycle is reached, the pH digital display will
ash, and the pH output relay will de-energize. The
controller must be reset manually by cycling out of
and back into the Auto mode using the mode buon.
- Selectable range: 20 to 100 cycles
b. If the Dose Time is set to a connuous feed mode,
the Over Timer will count in minutes. Default is 60
minutes.
- Selectable range: 20 to 180 minutes
3. When the Dose Time is changed from either med or
connuous feed, the Over Timer is reset to Default.
4. Turning o the Over Timer will void any NSF
Cercaon and is not recommended for safety
reasons.
18
M820 pH/Dual ORP Controller Owners Manual

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IPS Controllers M820 and is the answer not in the manual?

IPS Controllers M820 Specifications

General IconGeneral
BrandIPS Controllers
ModelM820
CategoryController
LanguageEnglish

Related product manuals