EasyManuals Logo

IPS Controllers M820 User Manual

IPS Controllers M820
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
e. High Alert
1. Default: 8.0 pH
2. Selectable range: OFF, 7.5 pH to 8.4 pH (acid feed). A
high alert will occur if the pH level remains above the
High Alert level for 10 connuous minutes, and will
automacally turn o the High Alert when the pH level
falls below the high alert level for 1 connuous minute.
During High Alert, the pH dose output will be disabled,
and by default ORP1 and ORP2 will be disabled (see Dip
Switch #2 sengs).
f. Low Alert
1. Default: 7.0 pH
2. Selectable range: OFF, 6.8 pH to 7.4 pH (acid feed). A
low alert will occur if the pH level remains below the
Low Alert level for 10 connuous minutes, and will
automacally turn o the Low Alert when the pH level
rises above the low alert level for 1 connuous minute.
During Low Alert, the pH dose output will be disabled.
g. pH Cal
1. Use to adjust pH to manually tested value.
2. Maximum increase/decrease is 0.9 pH within the 6.0 to
8.4 display window.
3. ORP1 standby
Note: While in this mode, the yellow ORP1 standby LED will
illuminate, both the pH and ORP digital displays will show dashes,
and all Auto funcons will be disabled. Use the Up or Down
arrow buons to the le to increase or decrease the funcon
value.
a. Set Level
1. Default: 650 mV
2. Selectable range: 400 mV to 900 mV (in 5 mV
increments)
19
M820 pH/Dual ORP Controller Owners Manual

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IPS Controllers M820 and is the answer not in the manual?

IPS Controllers M820 Specifications

General IconGeneral
BrandIPS Controllers
ModelM820
CategoryController
LanguageEnglish

Related product manuals