e. High Alert
1. Default: 8.0 pH
2. Selectable range: OFF, 7.5 pH to 8.4 pH (acid feed). A
high alert will occur if the pH level remains above the
High Alert level for 10 connuous minutes, and will
automacally turn o the High Alert when the pH level
falls below the high alert level for 1 connuous minute.
During High Alert, the pH dose output will be disabled,
and by default ORP1 and ORP2 will be disabled (see Dip
Switch #2 sengs).
f. Low Alert
1. Default: 7.0 pH
2. Selectable range: OFF, 6.8 pH to 7.4 pH (acid feed). A
low alert will occur if the pH level remains below the
Low Alert level for 10 connuous minutes, and will
automacally turn o the Low Alert when the pH level
rises above the low alert level for 1 connuous minute.
During Low Alert, the pH dose output will be disabled.
g. pH Cal
1. Use to adjust pH to manually tested value.
2. Maximum increase/decrease is 0.9 pH within the 6.0 to
8.4 display window.
3. ORP1 standby
Note: While in this mode, the yellow ORP1 standby LED will
illuminate, both the pH and ORP digital displays will show dashes,
and all Auto funcons will be disabled. Use the Up or Down
arrow buons to the le to increase or decrease the funcon
value.
a. Set Level
1. Default: 650 mV
2. Selectable range: 400 mV to 900 mV (in 5 mV
increments)
19
M820 pH/Dual ORP Controller Owner’s Manual