b. Dose Time
1. Default: 10-second ORP feed relay energized and 5
minutes ORP feed relay de-energized (med dose me).
In the med dose cycle mode, the dose LED will ash
while dosing, and will illuminate steadily during the
delay poron of the med cycle. In connuous dose
mode, the dose LED will ash while dosing, and dosing
will connue unl ORP is 10 mV above Set Level.
2. Selectable range: OFF, CON (connuous), and Timed
(10 to 900 seconds ON)
c. Delay Time
1. Default: Delay me of 5 minutes between feed cycles
(med feed only). Aer dose me, the controller will
wait (delay) for the specied minutes before checking
the current level and dosing again if necessary.
2. Selectable range: 1 - 99 minutes.
d. Over Timer
1. Default: ON. The Over Timer does not automacally
reset. It must be reset by turning the controller o, then
on.
2. The Over Timer is interlocked with the Dose Time
selecon.
i. If the Dose Time is set to a med cycle, the Over
Timer will count med feed cycles. Every me the set
level is reached the Over Timer will reset the count.
If the set (default is 60 cycles) Over Timer cycle is
reached, the ORP digital display will ash, and the
ORP output relay will de-energize.