M820 pH/Dual ORP Controller Owner’s Manual
3. Selectable range in med feed: OFF, 20 – 100 feed
cycles. Selectable range in connuous feed: OFF, 20
– 180 minutes. When the Dose Time is changed from
either med or connuous feed, the Over Timer is reset
to Default.
4. Turning o the Over Timer will void any NSF
Cercaon and is not recommended for safety
reasons.
e. High Alert
1. Default: 900 mV
2. Selectable range: 650 mV to 900 mV, no OFF. A high
alert will occur if the ORP level remains above the
High Alert level for 10 connuous minutes, and will
automacally turn o the High Alert when the ORP
level falls below the high alert level for 1 connuous
minute. During High Alert, the ORP1 dose output will be
disabled.
f. Low Alert
1. Default: 100 mV
2. Selectable range: OFF, 100 mV to 640 mV. A low alert
will occur if the ORP level remains below the Low Alert
level for 10 connuous minutes, and will automacally
turn o the Low Alert when the ORP level rises above
the low alert level for 1 connuous minute. During Low
Alert, the ORP1 dose output will be disabled.
g. pH Cal disabled
4. ORP2 standby
Note: While in this mode, the yellow ORP2 standby LED will
illuminate, both the pH and ORP digital displays will show dashes,
and all Auto funcons will be disabled. Use the Up or Down
arrow buons to the le to increase or decrease the funcon
value.