EasyManuals Logo

IPS Controllers M820 User Manual

IPS Controllers M820
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
22
M820 pH/Dual ORP Controller Owners Manual
a. Set Level
1. Default: 640 mV
2. Selectable range: 400 mV to 890 mV (in 5 mV
increments), cannot be set for less than 10 mV below
the ORP1 set level.
b. Dose Time
1. Default: OFF. In the med dose cycle mode, the dose
LED will ash while dosing and illuminate steadily during
the delay poron of the med cycle. In connuous dose
mode, the dose LED will ash while dosing, and dosing
will connue unl ORP is 10 mV above Set Level.
2. Selectable range: OFF, CON (connuous), and Timed
(10 to 900 seconds ON)
c. Delay Time
1. Default: OFF. Delay me of 5 minutes between feed
cycles (med feed only). Aer dose me, the controller
will wait (delay) for the specied minutes before
checking the current level and dosing again if necessary.
2. Selectable range: 1 - 99 minutes.
d. Over Timer
1. Default: ON. The Over Timer does not automacally
reset. It must be reset by using the mode buon to
cycle out of auto and then back to auto mode.
2. The Over Timer is interlocked with the Dose Time
selecon.
3. If the Dose Time is set to a med cycle, the Over Timer
will count med feed cycles. Every me the set level is
reached the Over Timer will reset the count. If the set
(default is 60 cycles) Over Timer cycle is reached, the
ORP2 output relay will de-energize. ORP2 will not ash
ORP digital display if ORP2 overfeed occurs).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IPS Controllers M820 and is the answer not in the manual?

IPS Controllers M820 Specifications

General IconGeneral
BrandIPS Controllers
ModelM820
CategoryController
LanguageEnglish

Related product manuals